Adding to the old system:
The older inverter, a SunnyBoy SB 5000-TL, is rated for a nominal 5kW and with its 18 panels, 9 of each located on opposite faces of my east/west facing roof (the ridge line precisely oriented to true north-south) would, in real life, produce more than 3900 watts for only an hour or so around "local noon" on late spring/early fall summer days that were both exquisitely clear and very cool (e.g. below 70F, 21C). I decided that the new inverter need not be a 5kW unit so I chose the newer - and significantly less expensive SunnyBoy SB3.8 - an inverter nominally rated at 3.8kW. The rated efficiencies of the two inverters were pretty much identical - both in the 97% range.
Figure 1: The installed 3.8 kW inverter in operation with the 2kW "SPS" (Secure Power System) island power outlet shown below. Click on the image for a larger version. |
One reason for choosing this lower-power inverter was to stay within the bounds of the rating of my main house distribution panel. My older inverter, being rated for 5kW was (theoretically) capable of putting 22-25 amps onto the panel's bus, so a 30 amp breaker was used on that branch circuit while the new inverter, capable of about 16 amps needed only a 20 amp breaker. This combined, theoretical maximum of 50 amps (breaker current ratings, not actual, real-world current from the inverters and their panels!) was within the "120% rule" of my 125 amp distribution panel with its 100 amp main breaker: 120% of 125 amps is 150 amps, so my ability to (theoretically) pull 100 amps from the utility and the combined capacity of the two inverters (again, theoretically - not real-world) being 50 amps was within this rating.
Comment: The highest total power that power that I have seen from my system has been about 8000 watts - 3900 watts from the SB3.8 and just over 4100 watts from the SB 5000 for a maximum of about 36 amps at 220 volts (abnormally low line voltage!) or about 33 amps total with a more typical 240 volt feed-in - well under the "50 amp" maximum.
For the new panels I installed eighteen 295 watt Solarworld units - a slight upgrade over the older 285 watt Suniva modules already in place. In my calculations I determined that even with the new panels having approximately 3.5% more rated output (e.g. a peak of 5310 watts versus 5130 watts, assuming ideal temperature and illumination - the latter being impossible with the roof angles) that the new inverter would "clip" (e.g. it would hit its maximum output power while the panels were capable of even more power) only a few 10s of days per year - and this would occur for only an hour or so at most on each occasion. Since the ostensibly "oversized" panel array would be producing commensurately more power at times other than peak as well, I was not concerned about this occasional "clipping".
What was expected:
The two sets of panels, old and new, are located on the same roof with the old array being higher, nearer the ridge line and the new being just below. In my situation I get a bit of shading in the morning on the east side, and a slight amount in the very late afternoon/evening in mid summer on west side and the geometry of the trees that do this cause the shading of both the new and old systems to be almost identical.
With this in mind, I would have expected the two systems to behave nearly identically.
But they don't!
Differences in produced power:
Having the ability to obtain graphs of each system over the course of a day I was surprised when the production of the two, while similar, showed some interesting differences as the chart below shows.
What might be the cause of this difference?
Figure 3: The two parallel east-facing arrays, the older one being closer to the (north-south) peak of the roof. Click on the image for a larger version. |
Several possible explanations come to mind:
- The new panels are producing significantly more than their official ratings. A few percent would seem likely, but 10%?
- The older panels have degraded more than expected in the year that they have been in service.
- The two manufacturers rate their panels differently.
- There may be thermal differences. The "new" panels are lower on the roof and it is possible that the air being pulled in from the bottom by convection is cooler when it passes by the new panels, being warmer by the time it gets to the "old" panels. If we take at face value that 3.5% of the 10% difference is due to the rating - leaving 6.5% difference unaccounted, this would need only about a 16C (39F) average panel temperature difference, but the temperature differences do not appear to be that large!
- The new panels don't heat up in the sun as much as the old. The new panels, in the interstitial gap between individual cells and around the edges are white while the old panels are completely black, possibly reducing the amount of heating. Again, there doesn't seem to be a 16C (39F) difference.
- The new inverter is better at optimizing the power from the panels than the old one.
I suspect that it is a combination of several of the above factors, probably excluding #2, but I have no real way of knowing the amount of contribution of each. What is surprising to me is that I have yet to see any obvious clipping on the new system on the production graphs even though I have "caught" it pegged at about 3920 watts on several occasions during local noon, so it seems that my calculation of "several dozen of hours" per year where this might happen is about right.
I'll continue to monitor the absolute and relative performance of the two sets of panels to see how they track over time.
* * *
Update - June, 2018:
The differences noted above still persist. In comparing the overall power production results between this year and last, there are no obvious changes in the two systems.
[End]
This page stolen from "ka7oei.blogspot.com"
No comments:
Post a Comment
PLEASE NOTE:
While I DO appreciate comments, those comments that are just vehicles to other web sites without substantial content in their own right WILL NOT be posted!
If you include a link in your comment that simply points to advertisements or a commercial web page, it WILL be rejected as SPAM!