Showing posts with label AC powerwall. Show all posts
Showing posts with label AC powerwall. Show all posts

Wednesday, November 14, 2018

Tesla Powerwall RF sensitivity to RF transmissions - and how to deal with it.

This article is about my experience in causing RF interference to a Powerwall, but I have written on two other articles about amateur radio operation along with having a Tesla Powerwall - these articles may be found here:
Figure 1:
Left to right:  Back-up Gateway (BUG), disconnect, two Powerwalls.
The cable raceway is just out of view, below the BUG.
 The BUG controls everything and was likely being bothered by RF
energy conducted to it via the Ethernet cable.  While it is possible to
connect a Powerwall via wireless, the reported experiences of other
Powerwall owners is that this method is less reliable in
the long term than a hard-wired cable.
Click on the image for a larger version.
In the first article above ("Reducing RFI from the Tesla Powerwall 2) I mentioned that I may have had an experience with RF interference to the Powerwall - but that the circumstances were inconclusive:  There was another problem that may have caused the symptoms (e.g. one of the mains connections' clamps had not been tightened at the time of installation).

This time, I do have a tale to tell about radio frequency interference (RFI) to my Powerwall 2 system.

The history:

Years ago, because it was convenient, I placed my DSL modem in my ham shack. Other than low-level spurs from the modem's plug-in power supply (wall wart) which were easily solved, it never caused any problems - nor would my HF operation seem to bother my DSL modem - except on 160 meters when I ran more than about 50 watts.  I found this remarkable because the wire from the DSLAM (the distant interface from the phone company) came through the window only about a foot away from the windowed transmission line that carried the transmit RF power to the antenna.  At some point I dropped the POTS (Plain Old Telephone Service) dial-up in lieu of VOIP and at the network interface (the box outside the house) I disconnected the internal house wiring as it was no longer needed, back-feeding this internal wiring from the VOIP box to allow the continued use of the phones.

Several years ago I got a linear amplifier capable of full-legal power (1500 watts in the U.S.) to use on the HF bands to assist when conditions were poor and on some frequencies this high-power operation would cause intermittent drop-outs in Internet connectivity when I transmitted.  It seemed that the longer I operated, the fewer these drop-outs were, possibly due to the modem "re-training" itself to deal with the (apparently) degraded connections.

When I got the Powerwall its Ethernet connection came through the outside wall and into the house near the DSL modem as it was a convenient place to make the connection - and a UPS was already nearby.  I recently decided to relocate the DSL modem to another room, one farther away from the ham shack and closer to where the underground wire from the telephone company came into the house and this involved a bit of additional wiring of Ethernet cable, and since my entire house is effectively on a UPS (via the Powerwall) it didn't matter where I plugged it in now.

Without the DSL modem in the shack I installed another Ethernet switch to manage the multiple connections that were made at that point:  One to the shack computer, another to the garage's Ethernet (to provide Internet connectivity of the solar inverters), another to a KiwiSDR and yet another to another switch where even more things were connected.  Also on this switch is the Ethernet connection to the Powerwall.

On the blink:

I'd done the relocating of the networking gear earlier in the afternoon about a week and a half ago and it wasn't until that evening when I got around to tidying things up slightly and putting a transmitter on the air - in this case, my 630 meter (472-479 kHz) station - to make a few contacts.  When I keyed the transmitter - which produces about 75 watts of RF - the lights in the house dimmed, a UPS beeped and the lights went bright again - so I quickly un-keyed.

After swearing to myself and hoping that this was a coincidence I waited for a minute or two and tried again - with the same result:  The power flickered, the UPS beeped and the lights went back to normal.  Bringing up the Tesla app I looked at the Powerwall's back-up history and saw that I now had two outages, each less than 30 seconds:  That in itself was unusual because the Powerwall typically stays off the grid for a couple minutes even after utility power returns to make sure that the it is stable.

"$#!+", I thought to myself again!

I then powered up the HF station.  Things were OK on 75 meters at 100 and 1500 watts and things were also OK on 40 meters at 100 watts - but I triggered the same "blink" response at any power level above about 600 watts.

Now began the methodical investigation.  The first thing that I did was to disconnect the Ethernet connection to the Powerwall from the switch that I had just installed:  No problems at all on any frequency or power level.

This was getting interesting:  Why would connecting the Ethernet cause a problem?

Ethernet connections are supposed to have galvanic isolation via a transformer!  To be sure, there is a small amount of capacitive coupling between the two windings, but this was on the order of a few 10s of picofarads - not nearly enough to cause a problem at 630 meters - or so one would think!

I then grabbed another Ethernet switch - a small, in expensive Linksys 5-port switch and connected everything to it:  No problems.
Figure 2:
Inside the raceway where several cables - including the Class-2 Ethernet
RS-485 cables for the Neurio run.  This picture shows the bonding of the
CAT-5's shields to the raceway (yellow tape and the blue wire that connects
to a mounting screw of the raceway using a spade lug and star washer). 
Also visible are some snap-on RF chokes (round gray, square black).
As mentioned, simply grounding the shield did nothing to solve the RF
ingress issue since the energy was being conducted on the cable's internal
wires already:  It took the addition of the chokes here and elsewhere (see
the other photos) to reduce the level being conducted on the Ethernet cable.
There are no exposed conductors in this raceway so it is "safe" to work in.
Click on the image for a larger version.

At this point I may have been able to get away with using that small, cheap switch, but it was very old and it was "only" a 100 Mbps-capable switch which meant that it would be a bottleneck for traffic between computers.  I was also determined to make it such that I it would not matter to what I connected the Powerwall's Ethernet cable as I wished to avoid a future problems should I forget why it was there!

When shielded cable doesn't help:

A bit of investigation revealed that the CAT-5e cable to the Powerwall was shielded.  One might first think that this should have solved the problem - but you'd be wrong

Shielding is useful for containing energy within the cable and prevent it from radiating, but if the cable in question is, itself, longitudinally conducting RF energy from one place to another, this shielding has absolutely no useful effect on its own!  In other words, if a piece of equipment at one end is somehow allowing RF to be induced onto the Ethernet cable, shielding will do nothing at all to prevent the conduction of RF to the far end - and it may well make it worse!

Still, the shield might prove useful to allow shunting some of the RF current on the shield so out of due diligence I went outside to the electrical raceway below the Powerwall where the conduit - which is all metallic and bonded to everything else, including the Powerwall - that conveyed the Ethernet cable from the house.  There, I carefully opened the outer jacket of the cables and made a connection to the shields which I then bonded to the metal raceway as depicted in figure 2.

Figure 3:
Inside, showing both the cable that goes between the Powerwall and the
Neurio in the garage (the left-hand cable with the two white snap-on chokes
in a loop) and the Ethernet cable that connects between my switch and
the Powerwall.  The Ethernet not only has two of the white snap-on chokes,
but it several turns are also wound through a Mix 75 toroidal core, seen
near the upper-right corner of the picture.
While this was enough to stop RF susceptibility issues on the HF bands,
these devices did not offer enough choking inductance on the Ethernet
cable to prevent problems at 630 meters.  Another Ethernet choke was
wound on another Mix 75 toroidal core - See Figure 4.
Click on the image for a larger version.
Because I had previously installed some Ferrites on the Ethernet cable and the other (shielded) CAT-5 cable that made the RS-485 connection to the Neurio in my garage I was hoping that this bonding - and the self-capacitance of these cable, both of which were now bonded - would shunt the RF energy to it and solve the problem.

It didn't.

No surprise there.

I decided to get serious about the problem and started checking the ferrite devices that I'd previously installed.  Winding a few turns on each I measured the inductance and found that they did provide a reasonable amount of reactance at 40 meters - typically 5-10 microHenries which provides between 200 and 400 ohms of impedance at 7 MHz - but clearly, this was not enough as I was still having problems at 7 MHz.  This would be especially true at 630 meters where the reactance would be only a few 10s of ohms - hardly enough to significantly impede RF energy at that frequency.  I then began to rummage about through my collection of ferrites, running a few turns of wire through each.

It became clear that the devices that I had previously used were typically of "Mix 43" or similar, best-used for the higher HF frequencies (and into VHF):  A few turns through one of these will give 10-ish microHenries of inductance, but I needed far more than this so I switched my attention to finding "Mix 75" and "Mix 77" devices - ferrite material that had an order of magnitude or so more permeability and would also yield much higher impedance:  A few turns on these would yield the hundreds of microHenries and offer several kilo-ohms of reactance to better-block RF - especially at 630 and 2200 meters.

What finally worked:
Figure 4:
A high-inductance choke wound on a Mix 75 toroidal core using flat "Cat 6"
Ethernet cable.  This device offers a common-mode choking inductance of
several millihenries at LF, MF and lower HF frequencies and was required
to solve the problem of conducted RF on the Ethernet cable causing issues
with the Powerwall's back-up gateway.  This cable was inserted into the
Ethernet cable between the indoor switch and the Powerwall using a CAT-6
rated double-female joiner.  A combination of a very high
inductance choke like this and several snap-on chokes over several turns
like those seen in Figure 2 and 3 are recommended for broad-band attenuation
of conducted currents.
Flat Ethernet cable is preferred for this as it will better-retain its internal
geometry when wound as tightly as this while similarly-winding round
Ethernet cable in such a manner may impact its signal integrity and
reduce its maximum speed.
Click on the image for a larger version.

What I settled on was a combination of several things:
  • Several turns of the Ethernet cable through some Mix 75 snap-on chokes.  The use of several chokes and several turns maximizes the added inductance.  (see figures 2 and 3.)
  • Some more of the same snap-on chokes were placed over the RS-485 connection to the Neurio in the garage.  There wasn't evidence that RF energy was affecting this line, but I didn't want to take the chance.
  • As depicted in Figure 4 I wound a 6 foot length of flat CAT-6 Ethernet cable over a toroidal (ring) core of Mix 75 ferrite to provide a choking inductance of several milliHenries - several orders of magnitude higher inductance than the other ferrite devices.  This "bulk" inductance would be responsible for blocking RF energy at the 630 and 2200 meter bands at which I often operate.
  • Inside the raceway I placed some additional Mix 75 snap-on devices over both the Ethernet and RS-485 cables, each passing through the cores several times for maximum inductance.

By adding all of this ferrite I increased the impedance (at RF) of the common-mode current to hundreds (if not thousands) of ohms at all of the frequencies on which I am likely to operate.  It is to this effort that one must go to minimize conducted RF energy on such conductors.

Why did it matter which Ethernet switch I was using?  I'm not sure, but I suspect that the Gig-E switch is lacking complete galvanic isolation on at least some of its Ethernet ports.  This issue could occur not only if there is a shielded Ethernet cable with attached shielded connectors on each end - which would be a liability in this particular case - but also if there is some sort of balanced connection to the pairs themselves - such as would be present if the switch had POE (Power Over Ethernet) capability.  The manual for the switch indicates no POE capability, but there is definitely something different about it and the way it connects the cables!  Perhaps a similar model of this switch does have POE and there is, in fact some connection inside - but unless/until I tear it down to find out, I won't really know.

Afterward:
Figure 5:
The "pin" on the BUG (Back-Up Gateway) that I was
requested by Tesla to photograph and forward to them.
This is pin is normally hidden by a sticker, hence the
"void" residue on the metal. This pin moves left/right
to go on/off grid, respectively.
Click on the image for a larger version.

Several days after this event I got a telephone call from Tesla Powerwall support asking me to remove the sticker from my back-up gateway and see if the "pin" was visible.  When queried, the representative noted that they had recorded several "incidents" with my system - and time and dates of these correlated exactly with my RF interference issues:  I told her that as far as I was concerned, the issue was resolved - but they still insisted that I take a picture of the pin and forward it to them - See Figure 5.

Update:  I was contacted again by Tesla - and this time they asked "if I was able to move the pin".  Not having been asked to do this before, I did so when I was at home again and it did move:  To the right, the house was isolated from the grid and to the left, the house is tied to the grid.

Having forwarded this information, I have yet to hear back.  (Update:  I never did.)


Parts sources for ferrite devices: 

There are several sources of snap-on ferrite devices described on this page, including:
  • KF7P Metalwerx - link - Supplier of a variety of ferrite devices and many other things.  At the present time he stocks the "Mix 31" devices, but does not stock "Mix 75" snap-on cores at the time of posting, but he does have ferrite rings of both ferrite mixes.
  • Mouser Electronics - link - The "Mix 31" snap-on cores - P/N:  623-0444164181  (Fair-Rite P/N:  0444164181);  "Mix 75" snap-on cores - Mouser P/N:  623-0475164181  (Fair-Rite P/N: 0475164181).  Mouser Electronics has other sizes and mixes of these various devices, including toroids (rings).

Links to other articles about power supply noise reduction found at ka7oei.blogspot.com:

Other solar power related posts at ka7oei.blogspot.com:

This page stolen from blogspot.ka7oei.com

[End]


Wednesday, May 17, 2017

Teasing out the differences between the "AC" and "DC" versions of the Tesla PowerWall 2

Being naturally interested in such things, I've been following the announcements and information about the Tesla PowerWall 2 - the follow-on product of the (rarely seen - in the U.S., at least) "original" PowerWall.

Somewhat interestingly/frustratingly, clear, concise (and even vaguely) technical information on either version of the PowerWall 2 (yes, there are two versions - the "DC" and "AC") has been a bit difficult to find, so in my research, what have I found?

Comment:  It would appear that the "DC" version of the PowerWall 2 has been discontinued - or, at the very least, it not routinely offered.
This page or its contents are not intended to promote any of the products mentioned nor should it be considered to be an authoritative source.

It is simply a statement of opinion, conjecture and curiosity based on the information publicly available at the time of the original posting.

It is certain that as time goes on that information referenced on this page may be officially verified, become commonplace, or proven to be completely wrong.

Such is the nature of life!

The "DC" PowerWall 2:
  • Data sheets (two whole pages, each - almost!) for both the DC and AC versions of the PowerWall may be found here at this link - link.
Unless you have a "hybrid" solar inverter, this one is NOT for you - and if you had such an inverter, you'd likely already know it.  A "hybrid" inverter is one that is specifically designed to pass some of the energy from the PV array (solar panels) into storage, such as a battery and used that stored energy later.

Unlike its "AC" counterpart (more on this later) this version of the PowerWall 2 does NOT appear to have an AC (mains) connection of any type - let alone an inverter (neither are mentioned in the brochure) - but rather it is an energy back-up for the solar panels on the DC input(s) of the hybrid inverter.   "Excess" power from the panels may used to charge the battery and this stored energy could be used to feed the inverter when the load (e.g. house) exceeds that available from the panels - when it is cloudy, if there is a period in which the load exceeds the output of the PV array for a period of time or there is no sun at all (e.g. night).

Whether or not this version of the PowerWall can actually be (indirectly) charged via the AC mains (e.g.  via a hybrid inverter capable of working "backwards" to produce AC from the mains) would appear to depend entirely on the capability and configuration of the hybrid inverter and the system overall.

But, you might ask,why would you ever want to charge the battery from the utility rather than from solar?  You might want to do this if there were variable tariffs in your area - say, $0.30/kWh during the peak hours in the day, but only $0.15kWh at night - in which case it would make sense supplant the "expensive" power during the day with "cheap" power bought at night to charge it up:  Although there would be, perhaps, a 10% "round trip loss" in doing this, it would still save money overall and help "even out" the loading that a utility might see during peak hours.

Whether or not this system would be helpful in a power outage is also dependent on the nature of the inverter to which it is connected:  Most grid-tie solar converters become useless when the mains power disappears (e.g. cannot produce any power for the consumer - more on this later) - and this applies to both "series string" (e.g. a large inverter fed by high-voltage DC from a series of panels) and the "microinverter" (small inverters at each of the panels) topologies.  Inverters configured for "island" operation (e.g. "free running" in the absence of a live power grid) or ones that can safely switch between "grid tie" and "island" modes would seem to be appropriate if you use the DC PowerWall and you want to keep your house "powered up" when there is a grid failure.

In other words, if you have a typical PV system that involves grid-tie inverters (series string or microinverter) and you have no "islanding" capability at present, the "DC" Power Wall is not for you!

The "AC" PowerWall 2:
  • Data sheets (two whole pages, each - almost!) for both the DC and AC versions of the PowerWall may be found here - LINK.
While the "AC" version seems to have the same battery storage capacity as the "DC" version (e.g. approx. 13.5kWh) it also has an integrated inverter and charger that interfaces with the AC mains that is apparently capable of supporting any standard voltage from 100 to 277 volts, 50 or 60 Hz, split or single phase.  This inverter, rated for approximately 7kW peak and 5-ish kW continuous, is sufficient to run many households.  Multiple units may be "stacked" (e.g. connected in parallel-type configuration - up to nine of them, according to the data sheet linked above) for additional storage and capacity.
Unlike the "DC" version, all of the power inflow/outflow is via the AC power feed, which is to say, it will both output AC power via its inverter and charge its battery via that same connection.  What this means is that it need not (and cannot, really) be directly connect to the PV (photovoltaic) system.  What seems clear is that this version has some means of monitoring the net flow in to and out of the house and to/from the utility which means that the PowerWall could balance this out by "knowing" how much power it could use to charge its battery, or needed to output.

(The basic diagram of Figure 1, below, shows how such a system might be connected.  This diagram does not specifically represent a PowerWall, but rather how any battery-based inverter/charger system might be used to supply back-up power to a home in the past and future.)

Because its power would be connected "indirectly" via AC power connections to the PV system it should (in theory) work with either a series-string or microinverter-type system - or, maybe even if you have no solar at all if you simply want to charge it during times of lower tariffs and pull the charge back out again during high tariffs.

(The Tesla brochure simply says "Support for wide range of usage scenarios" under the heading "Operating Modes" - which could be interpreted many ways, but at the time of the original posting of this article I have not actually seen an "official" suggestion of a use without any sort of solar power.)

What might such a system look like - schematically, at least?

How might this version of the PowerWall operate?  First, let's take a look at a diagram of how any sort of battery/inverter/charger like this might be configured for a house.
Figure 1:
Diagram of a generic battery-based "whole house" backup system based on obvious requirements.  This is a very basic diagram, showing most of the needed components that would be required to interface a battery-based inverter/charger with a typical house's electrical system and a PV (PhotoVoltaic/solar) charging system.
For those not familiar with North American power systems, typical residences are fed with 240 volt, center-tapped service from the utility's step-down transformer with this center-tap grounded at the service entrance.  This allows most devices to operate at 120 volts while those that consume large amounts of power (ranges, electric water heaters, electric dryers, air conditioners, etc.) are connected to 240 volt circuit, which may or may not need the "neutral" lead at all.  In most other parts of the world there would be only "L1" and the "Neutral" operating at about 240 volts.
Click on the image for a larger version.

Referring to Figure 1, above:

Shown to the right of center is a switch that opens when the utility's power grid goes offline, isolating the house and the inverter/charger from the power grid and included in that is a voltage monitor (consisting of potential transducers, or "PTs") that can detect when the mains voltage has returned and stabilized and it is "safe" to reconnect to the grid.  The battery-based inverter/charger is connected across the house's mains so that it can both pull current from it to charge its battery as well as push power into the house in a back-up situation.

The "Net current monitoring" current transducers ("CTs") might be used to allow the inverter/charger to "zero out" the total current (and, thus power) coming in from and going out to the power grid (under normal situations) such as when its battery is being charged and extra power is being produced by the PV system, but also to control the charge rate just so that only that "extra" power from the PV system is being used to assure, as much as possible, a net-zero flow to/from the utility.  The "House Current monitoring" is used to determine how much current is being used by the entire house while the "PV current monitoring" is used to determine the contribution of the PV system.

Comment:
The "PV current monitoring" point is probably superfluous:  All the PowerWall need know is how much power is going in to or out of the utility (power grid) and how much power is going in to or out of the house's main panel, which also includes any solar generation.  The third factor - how much power the PowerWall is using/producing is going to be available from the PowerWalls' own built-in monitoring.
By knowing these things it is possible to determine how much excess/deficit their may be in terms of the production of the PV system with respect to actual usage by the household.  Not shown is the current monitoring that would, no doubt, be included in the inverter/charger itself.  Some of the shown current monitoring points may be redundant as this information could be determined in other ways, but are included for clarity.

Finally, a local network (data) connection is shown for both the inverter/charger and the PV system so that there is a possibility that they may communicate with each other, perhaps for control purposes, as well as communicate via the Internet so that statistics may be monitored and recorded and to allow firmware updates to be issued.

How it might operate in practice:

As can be seen in Figure 1 and determined from the explanation, we can see that the PV is connected to the input/output of the inverter/charger (which could be a PowerWall - or any other similar system) via the house wiring which means that there is a path to the PowerWall to charge its battery, and the same path out of it when it needs to supply power, along with means of monitoring power flow.

With a system akin to that depicted in Figure 1, consider these possible scenarios:
  1. Excess power is being produced by the PV system and put back into the grid and the PowerWall's battery is fully-charged.   Because the battery is fully-charged there is nowhere to put this extra power so it goes back into the grid, tracked by the utility's "Net Meter" in the same way that it would be without a PowerWall.
  2. Excess power is being produced by the PV system and the PowerWall's battery is not fully charged.  The PowerWall will pull the amount of "excess" power that the PV system would normally be putting into the grid and charge its own battery at that same rate resulting in a net-zero amount of power being put into the grid.
  3. More power is being consumed by the user's household than is being produced by the solar array.  Depending on the state-of-charge and configuration of the PowerWall it may produce enough power to make up for the difference between what the PV system is producing and the user's needs.  At night this could (in theory) be 100% of the usage if the system were so-configured.
  4. Tariff leveling.  It would be theoretically possible to configure it so that whether or not solar was present and the utility charged a higher daytime than nighttime power rate, one could charge overnight from the mains and put out power during the day to reduce the power costs overall and to help "level" the utility's load.
What about a power outage?

All of the above scenarios are to be expected - and they are more-or-less standard offerings for many of the battery-based products of this type - but what if the AC mains go down?  For the rest of this discussion we will ignore the "DC" version of the PowerWall as its capability would rely on the configuration of the user's hybrid inverter and its capabilities/configuration when it comes to supplying backup, "islanded" AC power although the combination of a DC power wall and the appropriate inverter could be functionally identical to an AC Power Wall.

As mentioned before, with a typical PV system - either "series string" (one large inverter) or distributed (e.g. "microinverter") - if the power grid goes offline the PV system becomes useless:  A PV system requires the power grid to be present to both synchronize itself and present an infinite "sink" into which it can always "push" all of the "extra" power power that it is producing.  Were such units to not shut down, dangerous voltages could be "back-fed" into the power grid and be a hazard to anyone who might be trying to repair it.  It is for this reason that all grid-tie inverters are, by law, required to go offline and/or disconnect themselves completely from the power grid during a mains power outage.

The "AC" version of the Tesla PowerWall's system includes a switch that automatically isolates the house from the utility's power grid when there is a power failure.  Once this switch has isolated the house from the power grid the inverter built into the PowerWall can supply power to the house - at least as long as its battery lasts.

What about charging the battery during a power outage?

Here is where it seems to get a bit tricky.

If all grid-tie inverter systems go offline when the power grid fails, is it possible to use it to assist, or even charge the PowerWall during a grid failure?  In other words, can you use power from your PV system to recharge the PowerWall's battery or, at the very least, supply at least some of the power to extend its battery run-time?

In corresponding with a company representative - and corroborated by data openly published by Telsa (see the FAQ linked near the bottom of this posting) - the answer would appear to be "yes" - but exactly how this works is not very clear.

Based on rather vague information and knowing the behavior of the components involved it would seem to need to work this way:
  • The power (utility) grid goes down.
    • The user's PV system goes offline with the failure of the grid.
    • The PowerWall's switch opens, isolating the house completely from the grid - aside from the ability to monitor when the power grid comes back up.
    • The inverter in the PowerWall now takes the load of the (now isolated) house, producing AC power.
Were this all that happened, the house would again go dark once the battery in the PowerWall or similar "back-up power system" was depleted, but there seems to be more to it than this when a PV system is involved, as in:
  • When the back-up power system's inverter goes online, the PV system again sees what looks like the power grid and comes back online.
    • As it does, the back-up power system monitors the total power consumption and usage and any excess power being produced by the PV system is used to charge its battery.
    • If the PV system is producing less power than is being used, the back-up power system will supply the difference:  Its battery will still be discharged, but at a lower rate.  The house will still go dark when the battery is fully discharged.
Comment: 

What if you run the Power Wall down to the point where it goes offline and then the sun comes out the next day:  Is it possible to "bootstrap" the system to cause the PV to go online and start charging the battery, or are you "stuck" in an "offline" state where you can't produce PV to charge the battery because there is no AC power, but you can't produce AC power to charge the battery?

It is entirely possible that the DC version of the Power Wall may be "immune" to this "catch-22" situation by allowing some "reserve" capacity to restart once PV power is again available for charging - but how would it know that?
But now it gets even trickier and a bit more vague.

What if there is extra power being produced by the PV system?

Grid tie PV systems expect the power grid to be an infinite sink of power - but what if, during a power failure, when your backup up system is standing in as the power grid, your PV system is producing 5kW of solar energy and your house/inverter is using only 2kW:  Where does the extra 3kW of production go if it cannot be infinitely sinked into the utility grid, and how does one keep the PV system from "tripping out" and going off line?

To illustrate the problem, let us bring up a related scenario where we have a generator instead of some sort of battery-based back-up power system system.

There is a very good reason why owners of grid-tie systems are warned against using it to "assist" a backup generator and using that generator as a substitute for the power grid.  What can happen is this:
  • The AC power goes out and the transfer switch connects the house to the generator.
  • The generator comes online and produces AC power.
  • If the AC power from the generator is stable enough (not all generators produce adequately stable power) the PV system will come back online thinking that the power grid has come back.
  • When the PV system comes back online and produces power, the generator's load decreases:  Most generator's motors will slightly speed up as the load is decreased.
    • When the generator's motor speeds up, the frequency goes high.  When this happens, the PV system will see that as unstable power and will go offline.
    • When the PV system goes off, the power is suddenly dumped on the generator and it is hit with the full load and slows back down.
  •  The cycle repeats, with the PV system and generator "fighting" each other as the PV system continually goes on and offline.
An even worse scenario is this:
  • The AC power goes out, the transfer switch connects the house to the generator.
  • The generator comes online and produces power.
  • The PV system comes up because it "sees" the generator as the power grid, but its producing, say, 5kW but the house is, at the moment, using 2kW.
  • The PV system, because it think that it is connected to the power grid, will try to shove that extra 3kW somewhere, causing one or more of the following to happen:
    • The generator to speed up as power is being "pushed" into it, its frequency will go high and trip the PV system offline, and/or:
    • If the PV system tries to push more power into the system than there is a place for it to go (e.g. the case, above, where the solar is producing 3kW more than is being used) the voltage will necessarily go up.  Assuming that the generator doesn't "overspeed" and trip-out and the frequency doesn't go up and trip the PV system offline, the PV system will increase the voltage, trying to "push" the extra power into a load where there is nowhere for it to go:
      • As the PV system tries to "push" its excess power into the generator, it will increase the output voltage.  At some point the PV system will trip out on overvoltage, and the same "on-off" cycle mentioned above will occur.
      • It is possible that the excess power from the PV will "motor" the generator (e.g. the input power tries to "spin" the generator/motor) - an extremely bad thing to do which will probably cause it to overheat and eventually be destroyed if this goes un-checked.
      • If it is an "inverter" type generator, it can't be "motored", but the excess power will probably cause the generator's inverter to get stuck in the same "trip out/restart" cycle or simply fault out in an "overload condition - or the inverter might even be damaged/destroyed.
If having extra power from a grid-tie inverter is so difficult to deal with, what could you do with extra power that the PV system might be producing?

What if we have excess power and nowhere to put it?

The question that comes to mind now is "What does the PV system do when the PowerWall's battery is fully-charged and there is no-where to put extra energy that might be being produced?"  Where we have is the situation where our PV system is producing 5kW but we are using only 2kW leaving an extra 3kW to go... where?

The answer to that question is not at all clear, but four possibilities come to mind:
  1. Divert the power elsewhere.  Some people with "island" systems utilize a feature of some solar power systems that indicate when excess power is available and use it to operate a diversion switch to shunt the excess power in an attempt to do something useful like run an electric water heater, pump water or simply produce waste heat with a large resistor bank.  Such features are usually available only on "island" systems (e.g. those that are entirely self-contained and not tied to the power grid) and with large battery banks.
  2. Disable the PV system temporarily.  If it is possible, simply disable the PV system for a while and drain, say, 5-10% of the power out of the back-up power system battery before turning it back on and recharging it.  This will cause the PV system to cycle on and offline, but it will do so relatively slowly and it should cause no harm.
  3. Tell the PV system to shut off.  One could somehow communicate with the PV system and "tell" it to produce only the needed amount of energy.  This is a bit of a fine line to walk, but it is theoretically possible provided such a feature is available on the PV system.
  4. Alter the power to cause the PV system to drop off-line.  One could, in theory, alter the conditions of the power being produced by the back-up power system inverter such that it causes the PV system to go offline and stay that way until it needs to come back online.
Analyzing the possibilities:

Let's eliminate #1 as that will not apply to a typical grid-tie system, so that leaves us with:

#2:  Disabling the PV system:

Of these three possibilities #2 would seem to be the most obvious and it could be done simply by having another switch/relay on the output of the PV system that disconnects it from the rest of the house, forcing it to go offline - but this has its complications.

For example, in my system the PV is connected into a separate sub-panel located in the garage:  If one were to disconnect this branch circuit entirely, the power in the garage would go on and off, depending on the state-of-charge of the PowerWall or other battery-based back-up power system.  Connecting a PV system to a sub-panel is not an unusual configuration as it is not uncommon to find them connected to sub-panels that feed other systems, say, the air conditioner, kitchen, etc. (e.g. wherever a suitable circuit is available) so I'm guessing that they do not do it this way - unless they do it at the point before the PV system connects to the panel.  Doing this would require a remotely-controlled switch in many situations - awkward to wire up in many situations, but not impossible.

As noted above, one would disable the PV system once the battery had fully charged but enable it again once the battery had run down a bit - say, to 90-95%.  This way, one would not be rapid-cycling the PV system and the vast majority of the back-up power system's battery storage capacity would be available.

While this, too, should work, I suspect that it is not the one that is used as the drawings in the brochures don't show any such connection - but then again, they don't show the main house disconnect that would have to be present - but it would probably work just fine if the PV system were to gracefully come back online when it was time to do so (e.g. no user intervention to "reset" anything.)

#4:  Alter the operating conditions to cause the PV system to go offline:

Then there is #4, and one interesting possibility comes to mind - and it may sound like a kludge, but it should work.

One of the parameters that could be altered would be the frequency at which the back-up power system's inverter operates (say, 2-3 Hz or so above and/or below the proper line frequency) and force the PV system offline with that variance.  Even though this minor frequency change is not likely to hurt anything (many generators' frequencies drift around much more than this with varying loads!) devices that use the power line frequency as a reference - such as clocks, and clocks within various appliances - would drift rather badly unless the frequency were "dithered" above and below the proper frequency so that its long term average was properly maintained.

I suspect that this is not a method that would be used, but it could work - at least in theory.

Edit - 20170719:
In digging around, I have determined that "dithering" the frequency is, in fact, one of several ways that is used by an battery-backed inverter to disable a PV inverter when the PV is producing more power than can be accommodated by the load and/or battery charger.  This system, called "Frequency Shift Power Control" (FSPC) by at least one manufacturer (e.g. SunnyBoy) is designed to do this very thing.

A description of this technique may be found in section 6 of the document "Use of PV Inverters in Off-Grid  and Backup Systems in North and  South America" by SMA (SunnyBoy) found at this link.

Whether or not this is a control method used by the Power Wall is not known at this time.
Edit - 20180502:
Now having had an operational PowerWall 2 system for some time, I can verify that it is, in fact the "frequency control" method that is used.  During a sunny day with the battery at about 90%, I disconnected my house from the utility and observed that the PowerWall was taking a charge from the PV system.  During this time I monitored the AC mains frequency in the house.
At 97-98% charge the mains frequency increased from 60.00Hz to 60.50 Hz over several minutes at which point my PV inverters shut down due to the frequency being out of tolerance.  As the charge level dropped back down to 95% or so, the frequency slowly returned to 60.00 Hz and eventually the PV inverters came back online.  I kept the mains power disconnected for several hours and the above cycle repeated continuously.
My SunnyBoy PV inverters will simply "drop" abruptly when the limit (60.50 Hz) is reached, but it is possible that there are inverters out there that will, at some point, more gradually throttle the power back above a certain frequency threshold.  While this scheme would be more "graceful", either method works just fine.
One side-effect of this method is that the average mains frequency is increased during those times where the PV inverter is to be disabled.  If we assume that one were running only on solar, and there were 3 peak solar production hours that this will occur 50% of the the time (e.g. about 90 minutes spent at 60.5 Hz during the day) this would mean that clocks that were synchronized to the mains frequencies (many plug-in digital clocks, most appliances) would run "fast" by about 45 seconds per day.  This difference is in mains frequency is small enough that motorized appliances will function just fine.
#3:  "Talk" to the PV system and control the amount of power that it is producing:

That leaves us with #3:  Communicate with the PV system and "tell" it (perhaps using the "ModBus" interface) to produce only enough power to "zero" out the net usage.

The problem with this method is that it would depend on the capabilities of the PV inverter system and require that they support such specific remote control functions.  While it is very possible that some do, this method would be limited to those so-equipped and compatibility across many brands/models could be difficult.

#3 and #2:  "Talk" to the PV system to turn it on and off as needed:

Included in #3 could be a variant of method #2 and that would be to send a command to the inverter via its network connection to simply shut down and come back online as needed to keep the battery between, say, 90% and 100% charge as mentioned above.

This second variant of #3 seems most likely as there as it is possible that there is some sort of set of commands capable of this that would be widely implemented across vendors and models.

* * *

What do I think the likelihood to be?

I'm betting on the second variant of #3 where a command is sent to the PV system to tell it to turn off - at least until there is, again, somewhere to "send" excess power - but #4 is looking increasingly likely.

* * *

Having said all of this, there is a product FAQ that was put out by Tesla that seems to confirm the basic analysis - that is, its ability to run "stand alone" in the event of a power failure and the charge be maintained if there is sufficient excess PV capacity - read that FAQ here - LINK.


I'm investigating getting a PowerWall 2 system to augment my PV generation and provide "whole house" backup.  In the process I have been researching how it works and interfaces with both the utility and my existing PV system.

While I have occasionally asked questions of representatives of  Tesla, nothing that they have said is anything that could not be easily found in publicly-released information on the internet and as of the original date of this posting I haven't signed anything that could possibly keep me from talking about it.

However all of its interfacing and connectivity is done, it should be interesting!
Additional information may be found on the GreenTech Media web site:  "The New Tesla Powerwall Is Actually Two Different Products" - LINK.  This article and follow-up comments seem to indicate that there were, at the time of their writing, there were only a few manufacturers of inverters, namely SolarEdge and SMA (a.k.a. SunnyBoy) with which Tesla was installing/interfacing their systems, perhaps indicating some version of #2 or #3, above.  Clearly, the comments, mostly from several months ago, are also offering various conjectures on how the system actually works.

* * *


Finally, if you can find more specific information - say from a public document or from others' experience and analysis that can add more to this, please pass it along!


[End]

This page stolen from "ka7oei.blogspot.com"